Southwire’s 600 or 1000 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Silicone free.
Conductor | Ground Wire | ||||||||
No. of Conductors | Size (AWG or kcmil) (mm2) | No. of Strands | Insulation Thickness (mils) (mm) | Size (AWG) | No. of Strands | Nom. OD (mils) (mm) | Nominal Total Weight (lbs/1000') (kgs/km) | Allowable Ampacity | |
582238 |
3
3
|
8 AWG
8 AWG
|
7
7
|
45
1.14
|
8
8
|
|
666
16.92
|
189
282
|
|
599619 |
3
3
|
3/0 AWG
3/0 AWG
|
15
15
|
55
1.40
|
4
4
|
|
1324
33.63
|
918
1367
|
|
563211 |
3
3
|
500 KCMIL
500 KCMIL
|
35
35
|
65
1.65
|
1
1
|
|
2090
53.10
|
2298
3420
|
|
580013 |
3
3
|
750 KCMIL
750 KCMIL
|
58
58
|
80
2.03
|
3/0
3/0
|
|
2526
64.18
|
3392
5049
|
|