Southwire’s 600 or 1000 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Sunlight Resistant - For Direct Burial - Silicone Free
Conductor | Ground Wire | ||||||||
No. of Conductors | Size (AWG or kcmil) (mm2) | No. of Strands | Insulation Thickness (mils) (mm) | Size (AWG) | No. of Strands | Nom. OD (mils) (mm) | Nominal Total Weight (lbs/1000') (kgs/km) | Allowable Ampacity | |
480590 |
3
3
|
8 AWG
8 AWG
|
7
7
|
45
1.14
|
10
10
|
|
688
17.49
|
327
487
|
|
480608 |
3
3
|
6 AWG
6 AWG
|
7
7
|
45
1.14
|
8
8
|
|
782
19.88
|
467
695
|
|
480616 |
3
3
|
4 AWG
4 AWG
|
7
7
|
45
1.14
|
8
8
|
|
806
20.48
|
612
911
|
|
480624 |
3
3
|
2 AWG
2 AWG
|
7
7
|
45
1.14
|
6
6
|
|
982
24.95
|
928
1381
|
|
480632 |
3
3
|
1 AWG
1 AWG
|
19
19
|
55
1.40
|
6
6
|
|
1106
28.09
|
1142
1700
|
|
480640 |
3
3
|
1/0 AWG
1/0 AWG
|
19
19
|
55
1.40
|
6
6
|
|
1200
30.49
|
1417
2109
|
|
480657 |
3
3
|
2/0 AWG
2/0 AWG
|
19
19
|
55
1.40
|
6
6
|
|
1295
32.91
|
1724
2565
|
|
480665 |
3
3
|
3/0 AWG
3/0 AWG
|
19
19
|
55
1.40
|
4
4
|
|
1399
35.54
|
2065
3074
|
|
480673 |
3
3
|
4/0 AWG
4/0 AWG
|
19
19
|
55
1.40
|
4
4
|
|
1494
37.95
|
2503
3725
|
|
480681 |
3
3
|
250 KCMIL
250 KCMIL
|
37
37
|
65
1.65
|
4
4
|
|
1619
41.14
|
2941
4376
|
|
480707 |
3
3
|
350 KCMIL
350 KCMIL
|
37
37
|
65
1.65
|
3
3
|
|
1910
48.52
|
4127
6142
|
|
480723 |
3
3
|
500 KCMIL
500 KCMIL
|
37
37
|
65
1.65
|
2
2
|
|
2167
55.05
|
5702
8485
|
|
593173 |
3
3
|
600 KCMIL
600 KCMIL
|
61
61
|
80
2.03
|
3/0
3/0
|
|
2417
61.41
|
7287
10844
|
|
554410 |
3
3
|
750 KCMIL
750 KCMIL
|
61
61
|
80
2.03
|
1
1
|
|
2694
68.44
|
8623
12833
|
|