Southwire’s Type TC-ER, PLTC, FPL, and NFPL Control Cable are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C in dry locations and 75°C in wet locations, 105°C for emergency overload, and 150°C for short circuit conditions. For uses in Class I, II, and III per NEC Article 725 and 760. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Oil and sunlight resistant.
Conductor | Ground Wire | ||||||||
No. of Conductors | Size (AWG or kcmil) (mm2) | No. of Strands | Insulation Thickness (mils) (mm) | Size (AWG) | No. of Strands | Nom. OD (mils) (mm) | Nominal Total Weight (lbs/1000') (kgs/km) | Allowable Ampacity | |
581276 |
2
2
|
14 AWG
14 AWG
|
7
7
|
15
0.38
|
|
|
323
8.20
|
67
99
|
|
581600 |
4
4
|
12 AWG
12 AWG
|
7
7
|
15
0.38
|
|
|
422
10.72
|
148
221
|
|
581567 |
5
5
|
10 AWG
10 AWG
|
7
7
|
20
0.51
|
|
|
588
14.95
|
289
430
|
|