Southwire’s 600 Volt Type TC-ER control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 75°C in wet locations and 90°C in dry locations, 105°C for emergency overload, and 150°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Sunlight Resistant - For Direct Burial - Silicone Free - VW-1 Rated.
Conductor | Ground Wire | ||||||||
No. of Conductors | Size (AWG or kcmil) (mm2) | No. of Strands | Insulation Thickness (mils) (mm) | Size (AWG) | No. of Strands | Nom. OD (mils) (mm) | Nominal Total Weight (lbs/1000') (kgs/km) | Allowable Ampacity | |
604843 |
2
2
|
16 AWG
16 AWG
|
26
26
|
15
0.38
|
|
|
292
7.42
|
45
67
|
|
604850 |
3
3
|
16 AWG
16 AWG
|
26
26
|
15
0.38
|
|
|
308
7.83
|
58
86
|
|
604868 |
4
4
|
16 AWG
16 AWG
|
26
26
|
15
0.38
|
|
|
333
8.48
|
70
104
|
|
604876 |
5
5
|
16 AWG
16 AWG
|
26
26
|
15
0.38
|
|
|
362
9.21
|
82
122
|
|
604892 |
7
7
|
16 AWG
16 AWG
|
26
26
|
15
0.38
|
|
|
393
9.98
|
108
161
|
|
604918 |
9
9
|
16 AWG
16 AWG
|
26
26
|
15
0.38
|
|
|
454
11.55
|
135
201
|
|
604942 |
12
12
|
16 AWG
16 AWG
|
26
26
|
15
0.38
|
|
|
510
12.96
|
175
260
|
|
604975 |
15
15
|
16 AWG
16 AWG
|
26
26
|
15
0.38
|
|
|
595
15.13
|
227
337
|
|
605014 |
19
19
|
16 AWG
16 AWG
|
26
26
|
15
0.38
|
|
|
625
15.88
|
275
409
|
|
605071 |
25
25
|
16 AWG
16 AWG
|
26
26
|
15
0.38
|
|
|
700
17.78
|
350
521
|
|
605121 |
30
30
|
16 AWG
16 AWG
|
26
26
|
15
0.38
|
|
|
767
19.49
|
413
614
|
|
605196 |
37
37
|
16 AWG
16 AWG
|
26
26
|
15
0.38
|
|
|
867
22.02
|
529
788
|
|
408484 |
2
2
|
14 AWG
14 AWG
|
7
7
|
15
0.38
|
|
|
305
7.75
|
56
84
|
|
408518 |
3
3
|
14 AWG
14 AWG
|
7
7
|
15
0.38
|
|
|
322
8.19
|
75
111
|
|
408542 |
4
4
|
14 AWG
14 AWG
|
7
7
|
15
0.38
|
|
|
351
8.94
|
95
141
|
|
408575 |
5
5
|
14 AWG
14 AWG
|
7
7
|
15
0.38
|
|
|
380
9.66
|
110
164
|
|
608836 |
6
6
|
14 AWG
14 AWG
|
7
7
|
15
0.38
|
|
|
416
10.59
|
130
194
|
|
408633 |
7
7
|
14 AWG
14 AWG
|
7
7
|
15
0.38
|
|
|
412
10.49
|
146
217
|
|
408740 |
9
9
|
14 AWG
14 AWG
|
7
7
|
15
0.38
|
|
|
490
12.45
|
190
282
|
|
605477 |
10
10
|
14 AWG
14 AWG
|
7
7
|
15
0.38
|
|
|
572
14.54
|
229
340
|
|
408807 |
12
12
|
14 AWG
14 AWG
|
7
7
|
15
0.38
|
|
|
573
14.57
|
257
382
|
|
412874 |
15
15
|
14 AWG
14 AWG
|
7
7
|
15
0.38
|
|
|
632
16.07
|
313
466
|
|
412908 |
19
19
|
14 AWG
14 AWG
|
7
7
|
15
0.38
|
|
|
690
17.53
|
396
589
|
|
608729 |
20
20
|
14 AWG
14 AWG
|
7
7
|
15
0.38
|
|
|
725
18.42
|
417
620
|
|
552133 |
25
25
|
14 AWG
14 AWG
|
7
7
|
15
0.38
|
|
|
802
20.39
|
507
755
|
|
552190 |
37
37
|
14 AWG
14 AWG
|
7
7
|
15
0.38
|
|
|
949
24.11
|
760
1131
|
|
408468 |
2
2
|
12 AWG
12 AWG
|
7
7
|
15
0.38
|
|
|
348
8.85
|
77
115
|
|
408526 |
3
3
|
12 AWG
12 AWG
|
7
7
|
15
0.38
|
|
|
369
9.38
|
109
162
|
|
408559 |
4
4
|
12 AWG
12 AWG
|
7
7
|
15
0.38
|
|
|
401
10.21
|
150
223
|
|
408583 |
5
5
|
12 AWG
12 AWG
|
7
7
|
15
0.38
|
|
|
438
11.15
|
183
273
|
|
608737 |
6
6
|
12 AWG
12 AWG
|
7
7
|
15
0.38
|
|
|
481
12.23
|
190
282
|
|
408641 |
7
7
|
12 AWG
12 AWG
|
7
7
|
15
0.38
|
|
|
477
12.13
|
238
354
|
|
408757 |
9
9
|
12 AWG
12 AWG
|
7
7
|
15
0.38
|
|
|
580
14.73
|
332
494
|
|
408815 |
12
12
|
12 AWG
12 AWG
|
7
7
|
15
0.38
|
|
|
657
16.70
|
425
633
|
|
412882 |
15
15
|
12 AWG
12 AWG
|
7
7
|
15
0.38
|
|
|
734
18.66
|
455
677
|
|
412916 |
19
19
|
12 AWG
12 AWG
|
7
7
|
15
0.38
|
|
|
772
19.61
|
563
837
|
|
552166 |
25
25
|
12 AWG
12 AWG
|
7
7
|
15
0.38
|
|
|
943
23.96
|
762
1134
|
|
552224 |
37
37
|
12 AWG
12 AWG
|
7
7
|
15
0.38
|
|
|
1064
27.04
|
1084
1613
|
|
408492 |
2
2
|
10 AWG
10 AWG
|
7
7
|
20
0.51
|
|
|
420
10.67
|
115
172
|
|
408534 |
3
3
|
10 AWG
10 AWG
|
7
7
|
20
0.51
|
|
|
446
11.34
|
160
238
|
|
408567 |
4
4
|
10 AWG
10 AWG
|
7
7
|
20
0.51
|
|
|
505
12.83
|
208
309
|
|
408591 |
5
5
|
10 AWG
10 AWG
|
7
7
|
20
0.51
|
|
|
565
14.36
|
258
384
|
|
408658 |
7
7
|
10 AWG
10 AWG
|
7
7
|
20
0.51
|
|
|
615
15.62
|
381
567
|
|
408765 |
9
9
|
10 AWG
10 AWG
|
7
7
|
20
0.51
|
|
|
715
18.18
|
502
747
|
|
408823 |
12
12
|
10 AWG
10 AWG
|
7
7
|
20
0.51
|
|
|
806
20.48
|
653
971
|
|
601666 |
19
19
|
10 AWG
10 AWG
|
7
7
|
20
0.51
|
|
|
993
25.22
|
904
1345
|
|