Southwire’s Machine Flex® tray power cables 600/1000 Volt conform to NFPA 79 and are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial and where superior electrical properties are desired. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC® 336.10. These cables are capable of operating continuously at the conductor temperature not in excess of 75°C in wet locations and 90°C in dry locations, 130°C for emergency overload, and 150°C for short circuit conditions. For uses in Class I, II, Division 2 hazardous locations per NEC® Article 501 and 502. Southwire’s machine tray cable is ideal to power CNC machines, grinding, cutting, metal forming, buffing, bottling equipment, conveyors, processing & packaging equipment, assembly lines, control panels, food and beverage, oil sands, plant expansion, wind energy and data centers. Multiple approvals for multiple applications. Cable is rated for -40°C cold impact. Two conductor cables contain no green/yellow ground.
Conductor | Ground Wire | ||||||||
No. of Conductors | Size (AWG or kcmil) (mm2) | No. of Strands | Insulation Thickness (mils) (mm) | Size (AWG) | No. of Strands | Nom. OD (mils) (mm) | Nominal Total Weight (lbs/1000') (kgs/km) | Allowable Ampacity | |
677323 |
4
4
|
8 AWG
8 AWG
|
168
168
|
30
0.76
|
8
8
|
|
700
17.78
|
375
558
|
|
677324 |
4
4
|
6 AWG
6 AWG
|
259
259
|
30
0.76
|
6
6
|
|
817
20.75
|
564
840
|
|
677325 |
4
4
|
4 AWG
4 AWG
|
420
420
|
40
1.02
|
4
4
|
|
969
24.61
|
832
1239
|
|
677326 |
4
4
|
2 AWG
2 AWG
|
651
651
|
40
1.02
|
2
2
|
|
1196
30.38
|
1268
1887
|
|