Southwire’s Machine Flex® Tray Control is a flexible 20 AWG 300/600V cable and suitable for machine tool, Power Limited Tray and Instrumentation Tray and both exposed run (PLTC-ER & ITC-ER) applications. This product conforms to the NFPA 79 and suited for use in wet and dry areas, conduits, ducts, troughs, trays and where superior electrical properties are desired. It has North American approvals, is CE RoHS-2 for universal use in, on and off the machines utilized in industrial manufacturing work centers. For use in Class 1 Div 2 locations per NEC 501 and 502. These cables can operate continuously at the conductor temperature not in excess of 90C, 130C for emergency overload and 150C for short circuit conditions. Suitable for use in CNC machines, processing and packaging equipment, assembly lines, control panels food and beverage and plant expansions.
Conductor | Ground Wire | ||||||||
No. of Conductors | Size (AWG or kcmil) (mm2) | No. of Strands | Insulation Thickness (mils) (mm) | Size (AWG) | No. of Strands | Nom. OD (mils) (mm) | Nominal Total Weight (lbs/1000') (kgs/km) | Allowable Ampacity | |
677517 |
18
18
|
20 AWG
20 AWG
|
26
26
|
15
0.38
|
|
|
519
13.18
|
146
218
|
|
677511 |
3
3
|
20 AWG
20 AWG
|
26
26
|
15
0.38
|
|
|
264
6.71
|
33
50
|
|
672434 |
4
4
|
20 AWG
20 AWG
|
26
26
|
15
0.38
|
|
|
285
7.24
|
41
60
|
|
672437 |
5
5
|
20 AWG
20 AWG
|
26
26
|
15
0.38
|
|
|
307
7.80
|
48
72
|
|
677513 |
7
7
|
20 AWG
20 AWG
|
26
26
|
15
0.38
|
|
|
331
8.41
|
60
89
|
|
677515 |
9
9
|
20 AWG
20 AWG
|
26
26
|
15
0.38
|
|
|
420
10.67
|
89
133
|
|
672439 |
12
12
|
20 AWG
20 AWG
|
26
26
|
15
0.38
|
|
|
453
11.51
|
105
156
|
|
677519 |
25
25
|
20 AWG
20 AWG
|
26
26
|
15
0.38
|
|
|
598
15.19
|
195
290
|
|