Southwire’s shielded Machine Flex® tray control cables 600/1000 Volt conform to NFPA 79 and are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 75°C in wet locations and 90°C in dry locations, 130°C for emergency overload, and 150°C for short circuit conditions. For uses in Class I, II, Division 2 hazardous locations per NEC® Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC® 336.10. Southwire’s shielded flexible machine tray cable is ideal for use in for use in CNC machines, grinding, cutting, metal forming, buffing, bottling equipment, conveyors, processing & packaging equipment, assembly lines, control panels, food and bever- age, oil sands, plant expansion, wind energy and data centers. Multiple approvals for multiple applications. Cable is rated for -40°C cold impact. Two conductor cables contain no green/yellow ground.
Conductor | Ground Wire | ||||||||
No. of Conductors | Size (AWG or kcmil) (mm2) | No. of Strands | Insulation Thickness (mils) (mm) | Size (AWG) | No. of Strands | Nom. OD (mils) (mm) | Nominal Total Weight (lbs/1000') (kgs/km) | Allowable Ampacity | |
677081 |
2
2
|
18 AWG
18 AWG
|
16
16
|
15
0.38
|
|
|
293
7.45
|
53
79
|
|
588460 |
3
3
|
18 AWG
18 AWG
|
16
16
|
15
0.38
|
|
|
320
8.13
|
63
94
|
|
588461 |
4
4
|
18 AWG
18 AWG
|
16
16
|
15
0.38
|
|
|
326
8.28
|
70
104
|
|
588462 |
5
5
|
18 AWG
18 AWG
|
16
16
|
15
0.38
|
|
|
353
8.97
|
83
123
|
|
588463 |
7
7
|
18 AWG
18 AWG
|
16
16
|
15
0.38
|
|
|
378
9.60
|
101
150
|
|
630837 |
9
9
|
18 AWG
18 AWG
|
16
16
|
15
0.38
|
|
|
442
11.23
|
130
193
|
|
588464 |
12
12
|
18 AWG
18 AWG
|
16
16
|
15
0.38
|
|
|
478
12.14
|
156
232
|
|
598625 |
18
18
|
18 AWG
18 AWG
|
16
16
|
15
0.38
|
|
|
576
14.63
|
222
331
|
|
598626 |
25
25
|
18 AWG
18 AWG
|
16
16
|
15
0.38
|
|
|
658
16.71
|
290
432
|
|
677082 |
2
2
|
16 AWG
16 AWG
|
26
26
|
15
0.38
|
|
|
321
8.16
|
66
99
|
|
588465 |
3
3
|
16 AWG
16 AWG
|
26
26
|
15
0.38
|
|
|
331
8.41
|
79
117
|
|
588466 |
4
4
|
16 AWG
16 AWG
|
26
26
|
15
0.38
|
|
|
360
9.14
|
94
140
|
|
588467 |
5
5
|
16 AWG
16 AWG
|
26
26
|
15
0.38
|
|
|
391
9.93
|
110
164
|
|
588468 |
7
7
|
16 AWG
16 AWG
|
26
26
|
15
0.38
|
|
|
427
10.85
|
135
201
|
|
630836 |
9
9
|
16 AWG
16 AWG
|
26
26
|
15
0.38
|
|
|
491
12.47
|
171
255
|
|
588469 |
12
12
|
16 AWG
16 AWG
|
26
26
|
15
0.38
|
|
|
562
14.27
|
220
328
|
|
598627 |
18
18
|
16 AWG
16 AWG
|
26
26
|
15
0.38
|
|
|
646
16.41
|
303
451
|
|
598628 |
25
25
|
16 AWG
16 AWG
|
26
26
|
15
0.38
|
|
|
746
18.95
|
398
592
|
|
677083 |
2
2
|
14 AWG
14 AWG
|
41
41
|
15
0.38
|
|
|
349
8.86
|
84
125
|
|
588470 |
3
3
|
14 AWG
14 AWG
|
41
41
|
15
0.38
|
|
|
363
9.22
|
102
152
|
|
588471 |
4
4
|
14 AWG
14 AWG
|
41
41
|
15
0.38
|
16
16
|
|
401
10.20
|
125
186
|
|
588472 |
5
5
|
14 AWG
14 AWG
|
41
41
|
15
0.38
|
|
|
431
10.95
|
144
215
|
|
588473 |
7
7
|
14 AWG
14 AWG
|
41
41
|
15
0.38
|
|
|
466
11.84
|
178
265
|
|
598629 |
12
12
|
14 AWG
14 AWG
|
41
41
|
15
0.38
|
|
|
623
15.82
|
298
443
|
|
598630 |
18
18
|
14 AWG
14 AWG
|
41
41
|
15
0.38
|
|
|
720
18.29
|
412
613
|
|
598631 |
25
25
|
14 AWG
14 AWG
|
41
41
|
15
0.38
|
|
|
875
22.23
|
583
867
|
|
677084 |
2
2
|
12 AWG
12 AWG
|
65
65
|
15
0.38
|
|
|
387
9.83
|
112
167
|
|
677194 |
3
3
|
12 AWG
12 AWG
|
65
65
|
15
0.38
|
|
|
416
10.58
|
143
213
|
|
588474 |
4
4
|
12 AWG
12 AWG
|
65
65
|
15
0.38
|
|
|
450
11.45
|
173
257
|
|
588476 |
5
5
|
12 AWG
12 AWG
|
65
65
|
15
0.38
|
|
|
489
12.42
|
207
308
|
|
588477 |
7
7
|
12 AWG
12 AWG
|
65
65
|
15
0.38
|
|
|
555
14.10
|
269
400
|
|
677085 |
2
2
|
10 AWG
10 AWG
|
105
105
|
20
0.51
|
|
|
455
11.56
|
160
238
|
|
677196 |
3
3
|
10 AWG
10 AWG
|
105
105
|
20
0.51
|
|
|
544
13.82
|
218
325
|
|
588478 |
4
4
|
10 AWG
10 AWG
|
105
105
|
20
0.51
|
|
|
574
14.58
|
269
400
|
|
588479 |
5
5
|
10 AWG
10 AWG
|
105
105
|
20
0.51
|
|
|
608
15.44
|
317
471
|
|
588480 |
7
7
|
10 AWG
10 AWG
|
105
105
|
20
0.51
|
|
|
658
16.71
|
395
587
|
|
643354 |
4
4
|
8 AWG
8 AWG
|
168
168
|
30
0.76
|
10
10
|
|
742
18.85
|
439
653
|
|
643356 |
4
4
|
6 AWG
6 AWG
|
259
259
|
30
0.76
|
6
6
|
|
885
22.48
|
669
995
|
|
643358 |
4
4
|
4 AWG
4 AWG
|
420
420
|
40
1.02
|
4
4
|
|
1057
26.85
|
998
1485
|
|
643360 |
4
4
|
2 AWG
2 AWG
|
651
651
|
40
1.02
|
8
8
|
|
1237
31.42
|
1411
2099
|
|