SPEC 45006 CU 600V EPR Insulation Thermoset LSZH-TS Jacket RHH/RHW-2. CT Rated 1/0 and Larger - Silicone Free

Power Cable 600Volt Single Conductor Copper, Ethylene Propylene Rubber (EPR) insulation RHH/RHW-2 USE-2 Thermoset SOLONON® Low Smoke Zero Halogen (LSZH-TS) Jacket. CT Rated 1/0 and Larger - Silicone Free

Download Category Specifications
Excel Table

Application

Southwire’s 600 Volt power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. CT Rated 1/0 and Larger - Silicone Free

Specifications

Select a set of products below for more information:
Conductor Ground Wire
No. of Conductors Size (AWG or kcmil) (mm2) No. of Strands Insulation Thickness (mils) (mm) Size (AWG) No. of Strands Nom. OD (mils) (mm) Nominal Total Weight (lbs/1000') (kgs/km) Allowable Ampacity
890660
1 1
8 AWG 8 AWG
7 7
15 0.38
268 6.81
74 111
890659
1 1
6 AWG 6 AWG
7 7
30 0.76
338 8.59
119 178
551088
1 1
2 AWG 2 AWG
7 7
30 0.76
438 11.13
258 384
561561
1 1
1/0 AWG 1/0 AWG
19 19
45 1.14
575 14.61
419 623
561560
1 1
2/0 AWG 2/0 AWG
19 19
45 1.14
617 15.67
512 762
581799
1 1
3/0 AWG 3/0 AWG
19 19
45 1.14
669 16.99
629 936
561556
1 1
4/0 AWG 4/0 AWG
19 19
45 1.14
711 18.06
771 1147
890658
1 1
500 KCMIL 500 KCMIL
37 37
65 1.65
1041 26.44
1775 2642
551091
1 1
750 KCMIL 750 KCMIL
61 61
65 1.65
1246 31.65
2625 3907

Standards & References

  • ASTM B3: Soft or Annealed Copper Wire
  • ASTM B8: Concentric-Lay-Stranded Copper Conductors
  • UL 44: Thermoset-Insulated Wires and Cables
  • UL 1685: Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-95-658: (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • CT USE: Sizes 1/0 AWG and Larger

Construction

  • Conductor: Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  • Binder Tape: Mylar Tape
  • Insulation: Ethylene Propylene Rubber (EPR) Type RHH/RHW-2 USE-2
  • Overall Jacket: Thermoset SOLONON® Low Smoke Zero Halogen (LSZH-TS) Silicone-Free Jacket