For exposed or concealed wiring in wet or dry locations. For use in ventilated, non-ventilated and ladder type cable troughs and ventilated flexible cableway in wet, dry, hazardous locations or direct buried. Sunlight Resistant. Typical applications are for control. lighting and power circuits in: pulp and paper mills, steel mills, food processing plants, commercial centers, mines, generating stations, refineries, industrial plants and chemical plants. Voltage 1000V CSA / 600V UL.
Conductor | Ground Wire | ||||||||
No. of Conductors | Size (AWG or kcmil) (mm2) | No. of Strands | Insulation Thickness (mils) (mm) | Size (AWG) | No. of Strands | Nom. OD (mils) (mm) | Nominal Total Weight (lbs/1000') (kgs/km) | Allowable Ampacity | |
583961 |
3
3
|
500 KCMIL
500 KCMIL
|
35
35
|
90
2.29
|
1
1
|
|
2731
69.38
|
3285
4889
|
|
584846 |
3
3
|
6 AWG
6 AWG
|
7
7
|
60
1.52
|
6
6
|
|
1199
30.47
|
537
798
|
|