SPEC 25040 CSA TECK 90 600V PVC CONTROL CABLE

600V Multi Conductor, 14-10 AWG Copper, FT4 - Flame Retardancy Rating, XLPE Insulation, Aluminum Interlocked Armour, Sunlight Resistant, -40°C - 90°C, Rated HL, AG14

Download Category Specifications
Excel Table

Application

For exposed or concealed wiring in wet or dry locations. For use in ventilated, non-ventilated and ladder type cable troughs and ventilated flexible cableway in wet, dry, or hazardous locations. Sunlight Resistant. Typical applications are for control. lighting and power circuits in: pulp and paper mills, steel mills, food processing plants, commercial centers, mines, generating stations, refineries, industrial plants and chemical plants.

  • -40°C - CSA Cold Bend and Impact Temperature -40°C - Min. Installation Temperature 90°C - Max. Continuous Operating Temperature

Specifications

Select a set of products below for more information:
Conductor Ground Wire
No. of Conductors Size (AWG or kcmil) (mm2) No. of Strands Insulation Thickness (mils) (mm) Size (AWG) No. of Strands Nom. OD (mils) (mm) Nominal Total Weight (lbs/1000') (kgs/km) Allowable Ampacity
562239
2 2
14 AWG 14 AWG
7 7
30 0.76
14 14
660 16.77
196 291
561778
25 25
14 AWG 14 AWG
7 7
30 0.76
14 14
1373 34.89
900 1340
561781
4 4
14 AWG 14 AWG
7 7
30 0.76
14 14
715 18.16
246 366
561788
5 5
14 AWG 14 AWG
7 7
30 0.76
14 14
753 19.13
274 408
562248
6 6
14 AWG 14 AWG
7 7
30 0.76
14 14
792 20.14
304 452
561789
7 7
14 AWG 14 AWG
7 7
30 0.76
14 14
792 20.14
323 480
562254
8 8
14 AWG 14 AWG
7 7
30 0.76
14 14
864 21.97
375 559
562258
10 10
14 AWG 14 AWG
7 7
30 0.76
14 14
956 24.29
440 655
561790
12 12
14 AWG 14 AWG
7 7
30 0.76
14 14
977 24.83
481 716
562263
15 15
14 AWG 14 AWG
7 7
30 0.76
14 14
1044 26.52
554 825
561791
19 19
14 AWG 14 AWG
7 7
30 0.76
14 14
1199 30.45
694 1033
562269
20 20
14 AWG 14 AWG
7 7
30 0.76
14 14
1226 31.14
721 1074
561778
25 25
14 AWG 14 AWG
7 7
30 0.76
14 14
1373 34.89
900 1340
562275
30 30
14 AWG 14 AWG
7 7
30 0.76
14 14
1428 36.27
1009 1501
561792
2 2
12 AWG 12 AWG
7 7
30 0.76
14 14
695 17.66
223 332
561792
2 2
12 AWG 12 AWG
7 7
30 0.76
14 14
695 17.66
222 331
561794
4 4
12 AWG 12 AWG
7 7
30 0.76
14 14
757 19.24
292 435
589296
5 5
12 AWG 12 AWG
7 7
30 0.76
14 14
800 20.33
330 492
567116
6 6
12 AWG 12 AWG
7 7
30 0.76
14 14
876 22.27
393 585
568599
8 8
12 AWG 12 AWG
7 7
30 0.76
14 14
923 23.45
461 687
563506
10 10
12 AWG 12 AWG
7 7
30 0.76
14 14
1026 26.08
547 814
563511
15 15
12 AWG 12 AWG
7 7
30 0.76
14 14
1285 32.65
814 1211
563515
20 20
12 AWG 12 AWG
7 7
30 0.76
14 14
1375 34.94
978 1456
587679
30 30
12 AWG 12 AWG
7 7
30 0.76
14 14
1515 38.48
1296 1928
562290
2 2
10 AWG 10 AWG
7 7
30 0.76
12 12
747 18.97
273 406
561797
3 3
10 AWG 10 AWG
7 7
30 0.76
12 12
775 19.69
320 476
561798
4 4
10 AWG 10 AWG
7 7
30 0.76
12 12
819 20.83
372 553
567109
6 6
10 AWG 10 AWG
7 7
30 0.76
12 12
948 24.08
503 748
584443
8 8
10 AWG 10 AWG
7 7
30 0.76
12 12
1008 25.62
602 896
567096
10 10
10 AWG 10 AWG
7 7
30 0.76
12 12
1274 32.36
816 1214
589343
12 12
10 AWG 10 AWG
7 7
30 0.76
12 12
1301 33.07
909 1352
567102
15 15
10 AWG 10 AWG
7 7
30 0.76
12 12
1407 35.74
1069 1591

Standards & References

  • ASTM B3: Soft or Annealed Copper Wire
  • ASTM B8: Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 174: Cables in Hazardous Locations
  • CSA C22.2 No. 131: Type TECK 90 Cable
  • CSA C22.2 No. 2556 & No. 0.3: Wire and Cable Test Methods
  • CSA: LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA: HL - for Hazardous Locations rating
  • CSA: SUN RES - for Sunlight Resistant rating
  • CSA: AG14 - Acid Gas Compliance
  • IEEE 383: Flame Test (70,000 btu)
  • IEEE 1202: FT4 Flame Test (70,000) BTU/hr Vertical Tray Test

Construction

  • Conductor: Class B stranded copper, compressed or compact, in accordance with ASTM B3 and B8.
  • Insulation: Cross-Linked Polyethylene (XLPE), Colour Code: 2/C black, white; 3/C red, black, blue; 4/C red, black, blue, white; For 5/C cables or more, the insulation is black and numbered
  • Grounding Conductors: Uninsulated Class B stranded grounding conductor
  • Inner Jacket: Black Polyvinyl Chloride (PVC)
  • Armor: Aluminum Interlocked Armour (AIA)
  • Overall Jacket: Black PVC (optional colours available)

Resources