Southwire’s 15KV cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial when installed with a grounding conductor in close proximity that conforms to NEC section 311.36 and 250.4(A)(5), and where su- perior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated at -35°C for cold bend when UL listed. Rated at -25°C for cold bend and cold impact and marked with "LTDD" when CSA listed or dual UL/CSA listed. PVC jacket is made with SIM technology and has a coefficient of friction COF of 0.2. Cable can be installed in conduit without the aid of lubrication. Rated for 1000 lbs./FT maximum sidewall pressure.
Conductor | Ground Wire | ||||||||
No. of Conductors | Size (AWG or kcmil) (mm2) | No. of Strands | Insulation Thickness (mils) (mm) | Size (AWG) | No. of Strands | Nom. OD (mils) (mm) | Nominal Total Weight (lbs/1000') (kgs/km) | Allowable Ampacity | |
647203 |
1
1
|
1/0 AWG
1/0 AWG
|
19
19
|
220
5.59
|
|
|
1054
26.77
|
800
1191
|
|
647207 |
1
1
|
350 KCMIL
350 KCMIL
|
35
35
|
220
5.59
|
|
|
1342
34.09
|
1747
2600
|
|
553998 |
1
1
|
500 KCMIL
500 KCMIL
|
35
35
|
220
5.59
|
|
|
1470
37.34
|
2301
3425
|
|
561603 |
1
1
|
750 KCMIL
750 KCMIL
|
61
61
|
220
5.59
|
|
|
1735
44.07
|
3332
4958
|
|