Southwire’s 5KV cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial when installed with a grounding conductor in close proximity that conforms to NEC section 311.36 and 250.4(A)(5), and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated at -35°C for cold bend when UL listed. Rated at -25°C for cold bend and cold impact and marked with "LTDD" when CSA listed or dual UL/CSA listed. PVC jacket is made with SIM technology and has a coefficient of friction COF of 0.2. Cable can be installed in conduit without the aid of lubrication. Rated for 1000 lbs./FT maximum sidewall pressure.
Conductor | Ground Wire | ||||||||
No. of Conductors | Size (AWG or kcmil) (mm2) | No. of Strands | Insulation Thickness (mils) (mm) | Size (AWG) | No. of Strands | Nom. OD (mils) (mm) | Nominal Total Weight (lbs/1000') (kgs/km) | Allowable Ampacity | |
560182 |
1
1
|
2 AWG
2 AWG
|
7
7
|
115
2.92
|
|
|
790
20.07
|
343
510
|
|
559953 |
1
1
|
1/0 AWG
1/0 AWG
|
10
10
|
115
2.92
|
|
|
814
20.68
|
378
562
|
|
560116 |
1
1
|
2/0 AWG
2/0 AWG
|
12
12
|
115
2.92
|
|
|
884
22.45
|
447
665
|
|
560134 |
1
1
|
4/0 AWG
4/0 AWG
|
19
19
|
115
2.92
|
|
|
983
24.97
|
569
847
|
|
560135 |
1
1
|
350 KCMIL
350 KCMIL
|
35
35
|
115
2.92
|
|
|
1132
28.75
|
778
1157
|
|
560147 |
1
1
|
500 KCMIL
500 KCMIL
|
35
35
|
115
2.92
|
|
|
1274
32.36
|
990
1474
|
|
560179 |
1
1
|
750 KCMIL
750 KCMIL
|
58
58
|
115
2.92
|
|
|
1446
36.73
|
1316
1958
|
|
560180 |
1
1
|
1000 KCMIL
1000 KCMIL
|
58
58
|
115
2.92
|
|
|
1598
40.59
|
1628
2422
|
|