SPEC 46002 CU Compressed NLEPR Insulation 100% IL SIM-PVC Jacket. MV 90

Type MV-90 Single Conductor Copper, No Lead Ethylene Propylene Rubber (NL-EPR) SIMpull Polyvinyl Chloride (PVC) Jacket

Download Category Specifications
PDF Excel Table

Application

Southwire’s 2.4KV cables are suited for use in wet and dry areas, conduits, ducts, troughs, direct burial, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation, 130°C for emergency overload, and 250°C for short circuit conditions. Rated at -35°C for cold bend when UL listed. Rated at -25°C for cold bend and cold impact and marked with "LTDD" when CSA listed or dual UL/CSA listed. PVC jacket is made with SIM technology and has a coefficient of friction COF of 0.2. Cable can be installed in conduit without the aid of lubrication. Rated for 1000 lbs./FT maximum sidewall pressure.

Specifications

Select a set of products below for more information:
Conductor Ground Wire
No. of Conductors Size (AWG or kcmil) (mm2) No. of Strands Insulation Thickness (mils) (mm) Size (AWG) No. of Strands Nom. OD (mils) (mm) Nominal Total Weight (lbs/1000') (kgs/km) Allowable Ampacity
607457
1 1
2 AWG 2 AWG
7 7
125 3.18
746 18.95
413 615
607465
1 1
1 AWG 1 AWG
19 19
125 3.18
786 19.96
484 720
607226
1 1
1/0 AWG 1/0 AWG
19 19
125 3.18
826 20.98
568 846
607234
1 1
2/0 AWG 2/0 AWG
19 19
125 3.18
871 22.12
672 1000
607242
1 1
3/0 AWG 3/0 AWG
19 19
125 3.18
955 24.26
831 1236
607259
1 1
4/0 AWG 4/0 AWG
19 19
125 3.18
995 25.27
978 1456
607267
1 1
250 KCMIL 250 KCMIL
37 37
140 3.56
1112 28.24
1180 1756
607283
1 1
350 KCMIL 350 KCMIL
37 37
140 3.56
1207 30.66
1531 2279
607309
1 1
500 KCMIL 500 KCMIL
37 37
140 3.56
1332 33.83
2052 3054
607119
1 1
750 KCMIL 750 KCMIL
61 61
155 3.94
1611 40.92
3038 4521
607325
1 1
1000 KCMIL 1000 KCMIL
61 61
155 3.94
1761 44.73
3893 5794

Standards & References

  • ASTM B3: Soft or Annealed Copper Wire
  • ASTM B8: Concentric-Lay-Stranded Copper Conductors
  • ASTM B33: Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • ASTM B496: Compact Round Concentric-lay-standard copper
  • UL 1072: Medium-Voltage Power Cables
  • UL 1685: Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-93-639: (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA S-96-659: (NEMA WC 71) 2001-5000 V Nonshielded Cables
  • CT USE: Sizes 1/0 AWG and Larger
  • Made in America:: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661

Construction

  • Conductor: Class B compressed stranded bare copper per ASTM B3 and ASTM B8 (Tinned Copper per ASTM B33 optional)
  • Conductor Shield: Semi-conducting cross-linked copolymer
  • Insulation: No Lead Ethylene Propylene Rubber (NL-EPR)
  • Overall Jacket: Polyvinyl Chloride (PVC)

Resources