Southwire’s 600 Volt Type MC power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Silicone Free.
Conductor | Ground Wire | ||||||||
No. of Conductors | Size (AWG or kcmil) (mm2) | No. of Strands | Insulation Thickness (mils) (mm) | Size (AWG) | No. of Strands | Nom. OD (mils) (mm) | Nominal Total Weight (lbs/1000') (kgs/km) | Allowable Ampacity | |
644656 |
4
4
|
250 KCMIL
250 KCMIL
|
22
22
|
65
1.65
|
|
|
2019
51.29
|
1869
2782
|
|
644652 |
4
4
|
350 KCMIL
350 KCMIL
|
35
35
|
65
1.65
|
|
|
2250
57.17
|
2433
3620
|
|
640988 |
4
4
|
750 KCMIL
750 KCMIL
|
58
58
|
80
2.03
|
1/0
1/0
|
|
3062
77.78
|
4357
6484
|
|