Southwire’s 5KV TECK 90, 5000V, non-shielded, EPR insulated power cable is a CSA approved armoured cable for industrial and commercial medium voltage applications. FT4, -40°C, HL, AG14 and 90°C rated for use in harsh Canadian environments. Rated for installation in cable trays, duct banks, direct burial, troughs, hazardous locations, continuous rigid cable supports, and is concrete encaseable.
Conductor | Ground Wire | ||||||||
No. of Conductors | Size (AWG or kcmil) (mm2) | No. of Strands | Insulation Thickness (mils) (mm) | Size (AWG) | No. of Strands | Nom. OD (mils) (mm) | Nominal Total Weight (lbs/1000') (kgs/km) | Allowable Ampacity | |
568467 |
3
3
|
2 AWG
2 AWG
|
7
7
|
90
2.29
|
6
6
|
|
1695
43.06
|
1542
2294
|
|
568468 |
3
3
|
1 AWG
1 AWG
|
19
19
|
90
2.29
|
6
6
|
|
1792
45.53
|
1788
2661
|
|
568470 |
3
3
|
1/0 AWG
1/0 AWG
|
19
19
|
90
2.29
|
6
6
|
|
1878
47.72
|
2055
3059
|
|
568471 |
3
3
|
2/0 AWG
2/0 AWG
|
19
19
|
90
2.29
|
6
6
|
|
1984
50.39
|
2440
3631
|
|
568472 |
3
3
|
3/0 AWG
3/0 AWG
|
19
19
|
90
2.29
|
4
4
|
|
2092
53.14
|
2894
4307
|
|
568473 |
3
3
|
4/0 AWG
4/0 AWG
|
19
19
|
90
2.29
|
4
4
|
|
2245
57.04
|
3502
5212
|
|
568474 |
3
3
|
250 KCMIL
250 KCMIL
|
37
37
|
90
2.29
|
4
4
|
|
2358
59.89
|
3960
5893
|
|
568475 |
3
3
|
350 KCMIL
350 KCMIL
|
37
37
|
90
2.29
|
3
3
|
|
2637
66.98
|
5197
7734
|
|
568476 |
3
3
|
500 KCMIL
500 KCMIL
|
37
37
|
90
2.29
|
3
3
|
|
2863
72.74
|
6807
10129
|
|
Standard Specification for Soft or Annealed Copper Wire Concentric-Lay-Stranded Copper Conductors Type TECK 90 Cable Cables in Hazardous Locations Wire and Cable Test Methods LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating HL - for Hazardous Locations rating SUN RES - for Sunlight Resistant rating AG14 - Acid Gas Compliance (NEMA WC 71) 2001-5000 V Nonshielded Cables Flame Test (70,000 btu) FT4 Flame Test (70,000) BTU/hr Vertical Tray Test Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)