Used for secondary distribution and underground service at 600 volts or less, either direct burial or in ducts.
Conductor | Ground Wire | ||||||||
No. of Conductors | Size (AWG or kcmil) (mm2) | No. of Strands | Insulation Thickness (mils) (mm) | Size (AWG) | No. of Strands | Nom. OD (mils) (mm) | Nominal Total Weight (lbs/1000') (kgs/km) | Allowable Ampacity | |
554189 |
3
3
|
6 AWG
6 AWG
|
7
7
|
60
1.52
|
|
|
643
16.35
|
132
196
|
|
554187 |
3
3
|
4 AWG
4 AWG
|
7
7
|
60
1.52
|
|
|
744
18.91
|
188
280
|
|
554186 |
4
4
|
4 AWG
4 AWG
|
7
7
|
60
1.52
|
|
|
831
21.13
|
251
374
|
|
554174 |
3
3
|
2 AWG
2 AWG
|
7
7
|
60
1.52
|
|
|
870
22.11
|
275
409
|
|
554173 |
4
4
|
2 AWG
2 AWG
|
7
7
|
60
1.52
|
|
|
972
24.71
|
337
502
|
|
554150 |
3
3
|
1/0 AWG
1/0 AWG
|
9
9
|
80
2.03
|
|
|
1105
28.09
|
443
660
|
|
554148 |
4
4
|
1/0 AWG
1/0 AWG
|
9
9
|
80
2.03
|
|
|
1235
31.39
|
535
796
|
|
554163 |
3
3
|
2/0 AWG
2/0 AWG
|
11
11
|
80
2.03
|
|
|
1198
30.45
|
480
715
|
|
554160 |
4
4
|
2/0 AWG
2/0 AWG
|
11
11
|
80
2.03
|
|
|
1339
34.03
|
659
981
|
|
554183 |
3
3
|
4/0 AWG
4/0 AWG
|
18
18
|
80
2.03
|
|
|
1421
36.10
|
792
1178
|
|
554182 |
4
4
|
4/0 AWG
4/0 AWG
|
18
18
|
80
2.03
|
|
|
1588
40.35
|
971
1444
|
|
554168 |
3
3
|
250 KCMIL
250 KCMIL
|
22
22
|
95
2.41
|
|
|
1581
40.16
|
856
1274
|
|
554179 |
3
3
|
350 KCMIL
350 KCMIL
|
30
30
|
95
2.41
|
|
|
1794
45.59
|
1117
1662
|
|
554188 |
3
3
|
500 KCMIL
500 KCMIL
|
34
34
|
95
2.41
|
|
|
2064
52.45
|
1593
2371
|
|
Southwire’s quadruplex or paralleled 600 volt secondary UD cable meets or exceeds the following ASTM specifications:
Conductors are stranded, compressed 1350-H16/H26 aluminum, insulated with cross-linked polyethylene. Neutrals are identified by triple yellow extruded stripe. Cables with “YES” neutrals have sequential footage markers. Conductors are durably surface printed for identification. Three phase conductors and one neutral conductor are cabled together to produce the quadruplex cable configuration.