Southwire’s 2000 Volt power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions.
Conductor | Ground Wire | ||||||||
No. of Conductors | Size (AWG or kcmil) (mm2) | No. of Strands | Insulation Thickness (mils) (mm) | Size (AWG) | No. of Strands | Nom. OD (mils) (mm) | Nominal Total Weight (lbs/1000') (kgs/km) | Allowable Ampacity | |
597958 |
1
1
|
12 AWG
12 AWG
|
19
19
|
75
1.91
|
|
|
243
6.17
|
40
59
|
|
579962 |
1
1
|
10 AWG
10 AWG
|
19
19
|
75
1.91
|
|
|
263
6.68
|
53
80
|
|
569037 |
1
1
|
8 AWG
8 AWG
|
19
19
|
85
2.16
|
|
|
313
7.95
|
80
118
|
|
569039 |
1
1
|
6 AWG
6 AWG
|
19
19
|
85
2.16
|
|
|
349
8.86
|
114
170
|
|
569040 |
1
1
|
4 AWG
4 AWG
|
19
19
|
85
2.16
|
|
|
396
10.06
|
168
250
|
|
569043 |
1
1
|
1/0 AWG
1/0 AWG
|
19
19
|
105
2.67
|
|
|
570
14.48
|
397
590
|
|
569044 |
1
1
|
2/0 AWG
2/0 AWG
|
19
19
|
105
2.67
|
|
|
614
15.60
|
489
728
|
|
578324 |
1
1
|
500 KCMIL
500 KCMIL
|
37
37
|
120
3.05
|
|
|
1006
25.55
|
1685
2508
|
|