Southwire’s 600 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 75°C in wet locations and 90°C in dry locations, 105°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Sunlight Resistant - For Direct Burial - Silicone Free
Conductor | Ground Wire | ||||||||
No. of Conductors | Size (AWG or kcmil) (mm2) | No. of Strands | Insulation Thickness (mils) (mm) | Size (AWG) | No. of Strands | Nom. OD (mils) (mm) | Nominal Total Weight (lbs/1000') (kgs/km) | Allowable Ampacity | |
557694 |
4
4
|
8 AWG
8 AWG
|
7
7
|
30
0.76
|
10
10
|
|
701
17.81
|
384
571
|
|
553438 |
4
4
|
6 AWG
6 AWG
|
7
7
|
30
0.76
|
8
8
|
|
789
20.06
|
559
832
|
|
601989 |
4
4
|
4 AWG
4 AWG
|
7
7
|
40
1.02
|
8
8
|
|
933
23.70
|
877
1305
|
|
601997 |
4
4
|
2 AWG
2 AWG
|
7
7
|
40
1.02
|
6
6
|
|
1082
27.51
|
1230
1831
|
|
602003 |
4
4
|
1 AWG
1 AWG
|
19
19
|
50
1.27
|
6
6
|
|
1218
30.94
|
1545
2300
|
|
554568 |
4
4
|
1/0 AWG
1/0 AWG
|
19
19
|
50
1.27
|
6
6
|
|
1304
33.13
|
1851
2755
|
|
556720 |
4
4
|
2/0 AWG
2/0 AWG
|
19
19
|
50
1.27
|
6
6
|
|
1424
36.19
|
2264
3370
|
|
602029 |
4
4
|
3/0 AWG
3/0 AWG
|
19
19
|
50
1.27
|
4
4
|
|
1545
39.26
|
2819
4195
|
|
444745 |
4
4
|
4/0 AWG
4/0 AWG
|
19
19
|
50
1.27
|
4
4
|
|
1637
41.59
|
3287
4892
|
|
602045 |
4
4
|
250 KCMIL
250 KCMIL
|
37
37
|
60
1.52
|
4
4
|
|
1895
48.14
|
4113
6121
|
|
602060 |
4
4
|
350 KCMIL
350 KCMIL
|
37
37
|
60
1.52
|
3
3
|
|
2110
53.60
|
5448
8107
|
|
552513 |
4
4
|
500 KCMIL
500 KCMIL
|
37
37
|
60
1.52
|
2
2
|
|
2397
60.89
|
7485
11139
|
|
604819 |
4
4
|
600 KCMIL
600 KCMIL
|
61
61
|
70
1.78
|
2
2
|
|
2643
67.15
|
8924
13281
|
|