Southwire’s 600 Volt power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. CT Rated 1/0 and Larger - Silicone Free
Conductor | Ground Wire | ||||||||
No. of Conductors | Size (AWG or kcmil) (mm2) | No. of Strands | Insulation Thickness (mils) (mm) | Size (AWG) | No. of Strands | Nom. OD (mils) (mm) | Nominal Total Weight (lbs/1000') (kgs/km) | Allowable Ampacity | |
890660 |
1
1
|
8 AWG
8 AWG
|
7
7
|
15
0.38
|
|
|
268
6.81
|
74
111
|
|
890659 |
1
1
|
6 AWG
6 AWG
|
7
7
|
30
0.76
|
|
|
338
8.59
|
119
178
|
|
551088 |
1
1
|
2 AWG
2 AWG
|
7
7
|
30
0.76
|
|
|
438
11.13
|
258
384
|
|
561561 |
1
1
|
1/0 AWG
1/0 AWG
|
19
19
|
45
1.14
|
|
|
575
14.61
|
419
623
|
|
561560 |
1
1
|
2/0 AWG
2/0 AWG
|
19
19
|
45
1.14
|
|
|
617
15.67
|
512
762
|
|
581799 |
1
1
|
3/0 AWG
3/0 AWG
|
19
19
|
45
1.14
|
|
|
669
16.99
|
629
936
|
|
561556 |
1
1
|
4/0 AWG
4/0 AWG
|
19
19
|
45
1.14
|
|
|
711
18.06
|
771
1147
|
|
890658 |
1
1
|
500 KCMIL
500 KCMIL
|
37
37
|
65
1.65
|
|
|
1041
26.44
|
1775
2642
|
|
551091 |
1
1
|
750 KCMIL
750 KCMIL
|
61
61
|
65
1.65
|
|
|
1246
31.65
|
2625
3907
|
|