600V ROYAL® SOOW Cord Control with Black Jacket 90°C

600 Volt 90°C Flexible Cord. Heat, Moisture and Oil Resistant EPDM Rubber Insulation, Heat, Moisture and Oil Resistant Flexible CPE Jacket

Download Category Specifications
PDF Excel Table

Application

Southwire Type SOOW Flexible Cords UL/ CSA listed are permitted for use as specified by Article 400 and related articles of the 2014 National Electrical Code. The cable is rated -40°C to 90°C, water, oil, and weather resistant. Southwire Type SOOW Flexible Cords are designed for extra hard usage on industrial equipment, heavy tools, battery chargers, portable lights, welding leads, marine dockside power, power extensions and mining applications.

Specifications

Select a set of products below for more information:
Conductor
Size (AWG or kcmil) (mm2) No. of Conductors No. of Strands Nom. OD (mils) (mm) Nominal Total Weight (lbs/1000') (kgs/km) Allowable Ampacity Nom. DC Resistance (Conductor) Conductor Colors
558236
18 AWG 18 AWG
6 6
16 16
488 12.40
139 207
5.5 5.5
6.59 6.59
BLACK/WHITE/RED/GREEN/ORANGE/BLUE BLACK/WHITE/RED/GREEN/ORANGE/BLUE
558237
18 AWG 18 AWG
7 7
16 16
488 12.40
140 208
4.5 4.5
6.59 6.59
BLACK/WHITE/RED/GREEN/ORANGE/BLUE/WHITE-BLACK BLACK/WHITE/RED/GREEN/ORANGE/BLUE/WHITE-BLACK
558238
18 AWG 18 AWG
8 8
16 16
521 13.23
164 244
4.5 4.5
6.59 6.59
BLACK/RED-BLACK/WHITE-BLACK/BLUE/ORANGE/GREEN/RED/WHITE BLACK/RED-BLACK/WHITE-BLACK/BLUE/ORANGE/GREEN/RED/WHITE
570034
18 AWG 18 AWG
10 10
16 16
596 15.14
201 299
3.5 3.5
6.59 6.59
570037
18 AWG 18 AWG
12 12
16 16
605 15.37
218 324
3.5 3.5
6.59 6.59
598302
18 AWG 18 AWG
14 14
16 16
640 16.26
246 366
3.5 3.5
6.59 6.59
570039
18 AWG 18 AWG
16 16
16 16
668 16.97
274 408
3.5 3.5
6.59 6.59
570042
18 AWG 18 AWG
20 20
16 16
739 18.77
321 477
3.5 3.5
6.59 6.59
570043
18 AWG 18 AWG
24 24
16 16
830 21.08
398 592
3 3
6.59 6.59
571692
18 AWG 18 AWG
30 30
16 16
849 21.56
446 663
3 3
6.59 6.59
558232
16 AWG 16 AWG
6 6
26 26
516 13.11
169 251
8 8
4.05 4.05
BLACK/WHITE/RED/GREEN/ORANGE/BLUE BLACK/WHITE/RED/GREEN/ORANGE/BLUE
558233
16 AWG 16 AWG
7 7
26 26
564 14.33
203 302
7 7
4.05 4.05
BLACK/WHITE/RED/GREEN/ORANGE/BLUE/WHITE-BLACK BLACK/WHITE/RED/GREEN/ORANGE/BLUE/WHITE-BLACK
558234
16 AWG 16 AWG
8 8
26 26
515 13.08
192 285
7 7
4.05 4.05
BLACK/WHITE/RED/GREEN/ORANGE/BLUE/WHITE-BLACK/RED-BLACK BLACK/WHITE/RED/GREEN/ORANGE/BLUE/WHITE-BLACK/RED-BLACK
560526
16 AWG 16 AWG
10 10
26 26
648 16.46
277 412
5 5
4.05 4.05
560527
16 AWG 16 AWG
12 12
26 26
684 17.37
321 478
5 5
4.05 4.05
598305
16 AWG 16 AWG
14 14
26 26
727 18.47
340 506
5 5
4.05 4.05
560528
16 AWG 16 AWG
16 16
26 26
778 19.76
372 553
5 5
4.05 4.05
570018
16 AWG 16 AWG
20 20
26 26
745 18.92
397 591
5 5
4.05 4.05
570019
16 AWG 16 AWG
24 24
26 26
893 22.68
500 744
4.5 4.5
4.05 4.05
570026
16 AWG 16 AWG
30 30
26 26
982 24.94
647 963
4.5 4.5
4.05 4.05
558149
14 AWG 14 AWG
6 6
41 41
664 16.87
335 499
12 12
2.55 2.55
BLACK/WHITE/RED/GREEN/ORANGE/BLUE BLACK/WHITE/RED/GREEN/ORANGE/BLUE
558150
14 AWG 14 AWG
7 7
41 41
712 18.08
316 470
10 10
2.55 2.55
BLACK/WHITE/RED/GREEN/ORANGE/BLUE/WHITE-BLACK BLACK/WHITE/RED/GREEN/ORANGE/BLUE/WHITE-BLACK
558230
14 AWG 14 AWG
8 8
41 41
730 18.54
349 519
10 10
2.55 2.55
BLACK/WHITE/RED/GREEN/ORANGE/BLUE/WHITE-BLACK/RED-BLACK BLACK/WHITE/RED/GREEN/ORANGE/BLUE/WHITE-BLACK/RED-BLACK
569994
14 AWG 14 AWG
10 10
41 41
770 19.56
404 601
7 7
2.55 2.55
571270
14 AWG 14 AWG
12 12
41 41
883 22.43
477 710
7 7
2.55 2.55
569995
14 AWG 14 AWG
14 14
41 41
980 24.89
595 886
7 7
2.55 2.55
569997
14 AWG 14 AWG
16 16
41 41
1020 25.91
633 943
7 7
2.55 2.55
569999
14 AWG 14 AWG
24 24
41 41
1175 29.85
868 1291
6 6
2.55 2.55
558144
12 AWG 12 AWG
6 6
65 65
740 18.80
390 580
16 16
1.61 1.61
BLACK/WHITE/RED/GREEN/ORANGE/BLUE BLACK/WHITE/RED/GREEN/ORANGE/BLUE
558145
12 AWG 12 AWG
7 7
65 65
740 18.80
353 525
14 14
1.61 1.61
BLACK/WHITE-BLACK/BLUE/ORANGE/GREEN/RED/WHITE BLACK/WHITE-BLACK/BLUE/ORANGE/GREEN/RED/WHITE
558146
12 AWG 12 AWG
8 8
65 65
796 20.22
429 638
14 14
1.61 1.61
BLACK/WHITE/RED/GREEN/ORANGE/BLUE/WHITE-BLACK/RED-BLACK BLACK/WHITE/RED/GREEN/ORANGE/BLUE/WHITE-BLACK/RED-BLACK
571397
12 AWG 12 AWG
9 9
65 65
852 21.64
483 719
14 14
1.61 1.61
569981
12 AWG 12 AWG
10 10
65 65
894 22.71
501 745
10 10
1.61 1.61
569982
12 AWG 12 AWG
12 12
65 65
987 25.07
627 934
10 10
1.61 1.61
598307
12 AWG 12 AWG
14 14
65 65
1035 26.29
705 1049
10 10
1.61 1.61
598308
12 AWG 12 AWG
16 16
65 65
1089 27.66
810 1205
10 10
1.61 1.61
569983
12 AWG 12 AWG
20 20
65 65
1200 30.48
940 1398
10 10
1.61 1.61
569987
12 AWG 12 AWG
37 37
65 65
1536 39.01
1561 2322
8 8
1.61 1.61
569979
10 AWG 10 AWG
6 6
104 104
830 21.08
488 726
20 20
0.98 0.98
BLACK/WHITE/RED/GREEN/ORANGE/BLUE BLACK/WHITE/RED/GREEN/ORANGE/BLUE
569980
10 AWG 10 AWG
7 7
104 104
840 21.34
520 773
17 17
0.98 0.98
BLACK/WHITE-BLACK/BLUE/ORANGE/GREEN/RED/WHITE BLACK/WHITE-BLACK/BLUE/ORANGE/GREEN/RED/WHITE
570006
10 AWG 10 AWG
12 12
104 104
1067 27.10
848 1262
12 12
0.98 0.98

Standards & References

  • UL 62
  • CSA Standard 22.2 No. 49
  • NEC 400
  • NEC 501.140 Class I Division 2
  • Passes CSA FT2 Flame Test
  • MSHA
  • Federal and Military Specification JC-580B
  • RoHS-2 (European Directive 2011/65/EU )

Construction

  • Conductors: Class K stranded bare copper per ASTM B-174
  • Insulation: EPDM
  • Jacket: Black CPE (Other colors available upon request)