Southwire Tappan Fire Alarm

Southwire Tappan Fire Alarm

60°C 300V RISER RATED
Download Category Specifications:
PDF Excel Table

Application

FIRE PROTECTIVE SIGNALING POWER LIMITED CIRCUIT CABLE

Specifications

measurement
imperial metric
Select a set of products below for more information:
Conductor Ground Wire
No. of Conductors Size (AWG or kcmil) No. of Strands Insulation Thickness (mils) (mm) Size (AWG) No. of Strands Nom. OD (mils) (mm) Nominal Total Weight (lbs/1000') (kgs/km) Allowable Ampacity
F20427 4 4 22 AWG 22 AWG 1 1 118 3.00 11 17
F40015 2 2 18 AWG 18 AWG 1 1 153 3.89 17 25
F40003 4 4 18 AWG 18 AWG 1 1 154 3.91 26 38
G40503 6 6 18 AWG 18 AWG 1 1 184 4.67 41 60
F50004 2 2 16 AWG 16 AWG 1 1 154 3.91 21 31
F50382 4 4 16 AWG 16 AWG 1 1 202 5.13 42 62
F60001 2 2 14 AWG 14 AWG 1 1 190 4.83 32 48
F60112 4 4 14 AWG 14 AWG 1 1 224 5.69 60 90
F70004 2 2 12 AWG 12 AWG 1 1 232 5.89 49 73

Standards & References

UL 1424 FPLR, NEC article 760

  • UL 13 CL3R, NEC article 725
  • UL 444 CMR, NEC article 800
  • UL 1666 Vertical Riser / CSA FT4 (UL 1581)
  • CSA C22.2 CMG
  • RoHS (European Directive 22/95/EC)

Construction

Conductors: 22 AWG SOLID BARE COPPER

  • Insulation: PVC COLORS: BLACK, RED, GREEN, YELLOW
  • Shield/Drian: UNSHIELDED

Resources

There are no downloadable resources for this product.