Southwire’s 5KV cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated at -35°C for cold bend. For uses in Class I and II, Division 2 hazardous locations per NEC Article 501 and 502.Rated for 1000 lbs./FT maximum sidewall pressure.
Conductor | Ground Wire | ||||||||
No. of Conductors | Size (AWG or kcmil) | No. of Strands | Insulation Thickness (mils) (mm) | Size (AWG) | No. of Strands | Nom. OD (mils) (mm) | Nominal Total Weight (lbs/1000') (kgs/km) | Allowable Ampacity | |
556605 | 3 3 | 2 AWG 2 AWG | 7 7 | 115 2.92 | 6 6 | 1798 45.68 | 1808 2690 | ||
556613 | 3 3 | 1 AWG 1 AWG | 19 19 | 115 2.92 | 4 4 | 1893 48.10 | 2089 3109 | ||
556621 | 3 3 | 1/0 AWG 1/0 AWG | 19 19 | 115 2.92 | 4 4 | 1980 50.29 | 2333 3471 | ||
556639 | 3 3 | 2/0 AWG 2/0 AWG | 19 19 | 115 2.92 | 4 4 | 2075 52.71 | 2745 4085 | ||
556647 | 3 3 | 3/0 AWG 3/0 AWG | 19 19 | 115 2.92 | 3 3 | 2183 55.45 | 3191 4749 | ||
556654 | 3 3 | 4/0 AWG 4/0 AWG | 19 19 | 115 2.92 | 3 3 | 2273 57.75 | 3717 5531 | ||
556662 | 3 3 | 250 KCMIL 250 KCMIL | 37 37 | 115 2.92 | 2 2 | 2420 61.47 | 4580 6816 | ||
556670 | 3 3 | 350 KCMIL 350 KCMIL | 37 37 | 115 2.92 | 2 2 | 2617 66.49 | 5761 8573 | ||
556688 | 3 3 | 500 KCMIL 500 KCMIL | 37 37 | 115 2.92 | 1 1 | 2903 73.76 | 7650 11384 | ||
556696 | 3 3 | 750 KCMIL 750 KCMIL | 61 61 | 115 2.92 | 1/0 1/0 | 3386 86.00 | 10522 15659 |