Southwire’s 2.4KV cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 130°C for emergency overload, and 250°C for short circuit conditions. Rated at -35°C for cold bend. For uses in Class I and II, Division 2 hazardous locations per NEC Article 501 and 502.Rated for 1000 lbs./FT maximum sidewall pressure.
Conductor | Ground Wire | ||||||||
No. of Conductors | Size (AWG or kcmil) | No. of Strands | Insulation Thickness (mils) (mm) | Size (AWG) | No. of Strands | Nom. OD (mils) (mm) | Nominal Total Weight (lbs/1000') (kgs/km) | Allowable Ampacity | |
890086 | 3 3 | 2 AWG 2 AWG | 7 7 | 90 2.29 | 6 6 | 1393 35.40 | 1278 1902 | ||
606467 | 3 3 | 1/0 AWG 1/0 AWG | 19 19 | 90 2.29 | 4 4 | 1699 43.16 | 1918 2855 | ||
552212 | 3 3 | 2/0 AWG 2/0 AWG | 19 19 | 90 2.29 | 4 4 | 1796 45.63 | 2258 3360 | ||
552213 | 3 3 | 4/0 AWG 4/0 AWG | 19 19 | 90 2.29 | 3 3 | 1991 50.57 | 3119 4641 | ||
551526 | 3 3 | 350 KCMIL 350 KCMIL | 37 37 | 90 2.29 | 2 2 | 2349 59.66 | 4805 7151 | ||
890645 | 3 3 | 500 KCMIL 500 KCMIL | 37 37 | 90 2.29 | 1 1 | 2619 66.52 | 6483 9648 | ||
552256 | 3 3 | 750 KCMIL 750 KCMIL | 61 61 | 90 2.29 | 1/0 1/0 | 3089 78.48 | 9230 13736 |