500-37 CU 3C 90 MILS NL-EPR 2400V N/S WET/DRY 1X1 CU GW PVC JACKET

Southwire #: 60038799

Type MV-105 Three Conductor Copper, 90 Mils No Lead Ethylene Propylene Rubber (NL-EPR) Polyvinyl Chloride (PVC) Jacket

Download Category Specifications
PDF Excel Table
Select Product Specifications
Construction
Outer Jacket / Armor Color
Packaging

Application

Southwire’s 2.4KV cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated at -35°C for cold bend. For uses in Class I and II, Division 2 hazardous locations per NEC Article 501 and 502.Rated for 1000 lbs./FT maximum sidewall pressure.

Specifications

Stock # 60038799 60038799
No. of Conductors 3 3
Size (AWG or kcmil) (mm2) 500 KCMIL 500 KCMIL
No. of Strands 37 37
Insulation Thickness (mils) (mm) 90 2.29 mils mm
Size (AWG) 1 1
Nom. OD (mils) (mm) 2437 61.91 mils mm
Nominal Total Weight (lbs/1000') (kgs/km) 6310 9391 lbs/1000' kgs/km

Standards & References

Construction

Resources