Southwire’s 15KV cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerially supported by a messenger and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated at -35°C for cold bend. For uses in Class I and II, Division 2 hazardous locations per NEC Article 501 and 502.Rated for 1000 lbs./FT maximum sidewall pressure.
Conductor | Ground Wire | ||||||||
No. of Conductors | Size (AWG or kcmil) (mm2) | No. of Strands | Insulation Thickness (mils) (mm) | Size (AWG) | No. of Strands | Nom. OD (mils) (mm) | Nominal Total Weight (lbs/1000') (kgs/km) | Allowable Ampacity | |
956490 |
3
3
|
2 AWG
2 AWG
|
7
7
|
220
5.59
|
6
6
|
|
2032
51.62
|
2236
3328
|
|
958306 |
3
3
|
1/0 AWG
1/0 AWG
|
19
19
|
220
5.59
|
4
4
|
|
2215
56.28
|
2759
4105
|
|
956284 |
3
3
|
4/0 AWG
4/0 AWG
|
19
19
|
220
5.59
|
3
3
|
|
2516
63.91
|
4289
6382
|
|
558288 |
3
3
|
250 KCMIL
250 KCMIL
|
37
37
|
220
5.59
|
2
2
|
|
2628
66.76
|
4815
7166
|
|
958322 |
3
3
|
350 KCMIL
350 KCMIL
|
37
37
|
220
5.59
|
2
2
|
|
2935
74.56
|
6213
9247
|
|
958330 |
3
3
|
500 KCMIL
500 KCMIL
|
37
37
|
220
5.59
|
1
1
|
|
3162
80.33
|
7973
11866
|
|