Southwire® Type SEU, service entrance cable is primarily used to convey power from the service drop to the meter base and from the meter base to the distribution panelboard; however, the cable may be used in all applications where Type SE cable is permitted. SEU may be used in wet or dry locations at temperatures not to exceed 90°C. Voltage rating is 600 volts.
Stock # | 21828901 21828901 | |
Size (AWG or kcmil) (mm2) | 2/0 AWG 2/0 AWG | |
No. of Conductors | 2 2 | |
No. of Strands | 19 19 | |
Size (AWG) | 2/0 2/0 | |
No. of Neutrals | 1 1 | |
No. of Strands | 18 18 | |
Nom. Width (mils) (mm) | 1317 33.47 | mils mm |
Nom. Height (mils) (mm) | 791 20.11 | mils mm |
Nominal Total Weight (lbs/1000') (kgs/km) | 1447 2153 | lbs/1000' kgs/km |
Insulation Thickness (mils) (mm) | 55 1.40 | mils mm |
Allowable Ampacity at 60C | 145 145 | |
Allowable Ampacity at 75C | 175 175 | |
Allowable Ampacity at 90C | 195 195 | |
Allowable Ampacity in Dwelling | 200 200 |