Southwire’s 35KV cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated at -35°C for cold bend. ST1 (low smoke) Rated for sizes 1/0 and larger. Rated for 1000 lbs./FT maximum sidewall pressure. UV, sunlight and ozone resistant.
Conductor | Ground Wire | ||||||||
No. of Conductors | Size (AWG or kcmil) (mm2) | No. of Strands | Insulation Thickness (mils) (mm) | Size (AWG) | No. of Strands | Nom. OD (mils) (mm) | Nominal Total Weight (lbs/1000') (kgs/km) | Allowable Ampacity | |
890082 |
1
1
|
2/0 AWG
2/0 AWG
|
19
19
|
420
10.67
|
|
|
1524
38.71
|
1377
2049
|
|
890066 |
1
1
|
4/0 AWG
4/0 AWG
|
19
19
|
420
10.67
|
|
|
1616
41.05
|
1708
2542
|
|
890083 |
1
1
|
250 KCMIL
250 KCMIL
|
37
37
|
420
10.67
|
|
|
1728
43.89
|
1984
2952
|
|
890067 |
1
1
|
350 KCMIL
350 KCMIL
|
37
37
|
420
10.67
|
|
|
1827
46.41
|
2385
3550
|
|
679731 |
1
1
|
500 KCMIL
500 KCMIL
|
37
37
|
420
10.67
|
|
|
1952
49.58
|
2995
4458
|
|
890084 |
1
1
|
750 KCMIL
750 KCMIL
|
61
61
|
420
10.67
|
|
|
2164
54.97
|
3973
5912
|
|