RW90 SIMpull® Aluminum

Single 8000 Series Aluminum Conductor, 600V Alumaflex Strand, No. 6 AWG to 1000 KCMIL, 90°C MAX -40°C MIN, Sunlight Resistant.

Download Category Specifications
PDF Excel Table

Application

Southwire’s SIMpull ® aluminum RW90 is for open wiring used in raceways (except cabletroughs and ventilated flexible cableways) in dry or wet locations. For open wiring exposed to the weather. Minimum recommended installation temperature minus 40°C (with suitable handling procedures). Maximum conductor temperature 90°C.

Specifications

Select a set of products below for more information:
Conductor Allowable Ampacities
Size (AWG or kcmil) (mm2) No. of Strands Nom. OD (mils) (mm) Insulation Thickness (mils) (mm) Nominal Total Weight (lbs/1000') (kgs/km) Allowable Ampacity at 75°C Open Air Allowable Ampacity at 90°C Open Air Allowable Ampacity at 75°C Cable in Conduit Allowable Ampacity at 90°C Cable in Conduit
562497
6 AWG 6 AWG
7 7
265 6.73
45 1.14
40 60
75 75
85 85
50 50
55 55
562498
4 AWG 4 AWG
7 7
309 7.85
45 1.14
58 87
100 100
115 115
65 65
75 75
562499
2 AWG 2 AWG
6 6
364 9.25
45 1.14
86 128
135 135
150 150
90 90
100 100
561705
1 AWG 1 AWG
8 8
415 10.54
55 1.40
110 163
155 155
175 175
100 100
115 115
561667
1/0 AWG 1/0 AWG
10 10
452 11.48
55 1.40
134 199
180 180
205 205
120 120
135 135
562276
2/0 AWG 2/0 AWG
12 12
492 12.50
55 1.40
163 243
210 210
235 235
135 135
150 150
580901
3/0 AWG 3/0 AWG
16 16
539 13.69
55 1.40
200 298
240 240
270 270
155 155
175 175
560975
4/0 AWG 4/0 AWG
19 19
591 15.01
55 1.40
246 367
280 280
315 315
180 180
205 205
596076
300 KCMIL 300 KCMIL
21 21
708 17.98
65 1.65
350 521
350 350
395 395
230 230
260 260
560983
350 KCMIL 350 KCMIL
35 35
754 19.15
65 1.65
401 596
395 395
445 445
250 250
280 280
561598
400 KCMIL 400 KCMIL
35 35
797 20.24
65 1.65
453 674
425 425
480 480
270 270
305 305
592884
500 KCMIL 500 KCMIL
34 34
876 22.25
65 1.65
557 828
485 485
545 545
310 310
350 350
592887
600 KCMIL 600 KCMIL
37 37
983 24.97
80 2.03
681 1014
545 545
615 615
340 340
385 385
560985
750 KCMIL 750 KCMIL
61 61
1078 27.38
80 2.03
834 1241
620 620
700 700
385 385
435 435

Standards & References

Southwire’s SIMpull ® RW90 cables meet or exceed the following requirements:

  • Single aluminum conductor
  • CSA Spec. C22.2" No. 38
  • CSA FT4 Flame Test Rating - sizes 350 KCMIL and Larger
  • Sunlight Resistant
  • CSA File Listing: LL90458
  • Lead Free and RoHS compliant

Construction

Southwire’s SIMpull ® aluminum conductor RW90 with 8000 Series aluminum" low temperature rating" moisture resisting XLPE (cross linked polyethylene) and sunlight resistant insulation is marked "Sun Res" or "SR". Rated FT4 in sizes 350 KCMIL and larger. This product meets the current RoHS requirements and no lead is added or used in manufacturing.

  • Aluminum Conductor
  • SIMpull ® Insulation
  • Standard colours are available in black" red" blue" white and green.
  • Contact your Southwire rep for further availability details.