Southwire’s SIMpull ® aluminum RW90 is for open wiring used in raceways (except cabletroughs and ventilated flexible cableways) in dry or wet locations. For open wiring exposed to the weather. Minimum recommended installation temperature minus 40°C (with suitable handling procedures). Maximum conductor temperature 90°C.
Conductor | Allowable Ampacities | ||||||||
Size (AWG or kcmil) (mm2) | No. of Strands | Nom. OD (mils) (mm) | Insulation Thickness (mils) (mm) | Nominal Total Weight (lbs/1000') (kgs/km) | Allowable Ampacity at 75°C Open Air | Allowable Ampacity at 90°C Open Air | Allowable Ampacity at 75°C Cable in Conduit | Allowable Ampacity at 90°C Cable in Conduit | |
562497 |
6 AWG
6 AWG
|
7
7
|
265
6.73
|
45
1.14
|
40
60
|
75
75
|
85
85
|
50
50
|
55
55
|
562498 |
4 AWG
4 AWG
|
7
7
|
309
7.85
|
45
1.14
|
58
87
|
100
100
|
115
115
|
65
65
|
75
75
|
562499 |
2 AWG
2 AWG
|
6
6
|
364
9.25
|
45
1.14
|
86
128
|
135
135
|
150
150
|
90
90
|
100
100
|
561705 |
1 AWG
1 AWG
|
8
8
|
415
10.54
|
55
1.40
|
110
163
|
155
155
|
175
175
|
100
100
|
115
115
|
561667 |
1/0 AWG
1/0 AWG
|
10
10
|
452
11.48
|
55
1.40
|
134
199
|
180
180
|
205
205
|
120
120
|
135
135
|
562276 |
2/0 AWG
2/0 AWG
|
12
12
|
492
12.50
|
55
1.40
|
163
243
|
210
210
|
235
235
|
135
135
|
150
150
|
580901 |
3/0 AWG
3/0 AWG
|
16
16
|
539
13.69
|
55
1.40
|
200
298
|
240
240
|
270
270
|
155
155
|
175
175
|
560975 |
4/0 AWG
4/0 AWG
|
19
19
|
591
15.01
|
55
1.40
|
246
367
|
280
280
|
315
315
|
180
180
|
205
205
|
596076 |
300 KCMIL
300 KCMIL
|
21
21
|
708
17.98
|
65
1.65
|
350
521
|
350
350
|
395
395
|
230
230
|
260
260
|
560983 |
350 KCMIL
350 KCMIL
|
35
35
|
754
19.15
|
65
1.65
|
401
596
|
395
395
|
445
445
|
250
250
|
280
280
|
561598 |
400 KCMIL
400 KCMIL
|
35
35
|
797
20.24
|
65
1.65
|
453
674
|
425
425
|
480
480
|
270
270
|
305
305
|
592884 |
500 KCMIL
500 KCMIL
|
34
34
|
876
22.25
|
65
1.65
|
557
828
|
485
485
|
545
545
|
310
310
|
350
350
|
592887 |
600 KCMIL
600 KCMIL
|
37
37
|
983
24.97
|
80
2.03
|
681
1014
|
545
545
|
615
615
|
340
340
|
385
385
|
560985 |
750 KCMIL
750 KCMIL
|
61
61
|
1078
27.38
|
80
2.03
|
834
1241
|
620
620
|
700
700
|
385
385
|
435
435
|
Southwire’s SIMpull ® RW90 cables meet or exceed the following requirements:
Southwire’s SIMpull ® aluminum conductor RW90 with 8000 Series aluminum" low temperature rating" moisture resisting XLPE (cross linked polyethylene) and sunlight resistant insulation is marked "Sun Res" or "SR". Rated FT4 in sizes 350 KCMIL and larger. This product meets the current RoHS requirements and no lead is added or used in manufacturing.