Southwire’s 600 Volt Type TC-ER control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 75°C in wet locations and 90°C in dry locations, 105°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10.
Conductor | Ground Wire | ||||||||
No. of Conductors | Size (AWG or kcmil) (mm2) | No. of Strands | Insulation Thickness (mils) (mm) | Size (AWG) | No. of Strands | Nom. OD (mils) (mm) | Nominal Total Weight (lbs/1000') (kgs/km) | Allowable Ampacity | |
606806 |
3
3
|
14 AWG
14 AWG
|
7
7
|
15
0.38
|
14
14
|
|
349
8.88
|
90
134
|
|
606814 |
4
4
|
14 AWG
14 AWG
|
7
7
|
15
0.38
|
14
14
|
|
384
9.77
|
111
166
|
|
606723 |
3
3
|
12 AWG
12 AWG
|
7
7
|
15
0.38
|
12
12
|
|
364
9.27
|
132
196
|
|
606723 |
3
3
|
12 AWG
12 AWG
|
7
7
|
15
0.38
|
12
12
|
|
364
9.27
|
132
196
|
|
606798 |
4
4
|
12 AWG
12 AWG
|
7
7
|
15
0.38
|
12
12
|
|
406
10.33
|
158
235
|
|
605543 |
3
3
|
10 AWG
10 AWG
|
7
7
|
20
0.51
|
10
10
|
|
488
12.40
|
205
304
|
|
606863 |
4
4
|
10 AWG
10 AWG
|
7
7
|
20
0.51
|
10
10
|
|
565
14.36
|
259
386
|
|