Southwire’s 600 Volt power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. CT Rated 1/0 and Larger - Sunlight Resistant - Silicone Free. Rated for 1000 lbs./FT maximum sidewall pressure.
Conductor | Ground Wire | ||||||||
No. of Conductors | Size (AWG or kcmil) (mm2) | No. of Strands | Insulation Thickness (mils) (mm) | Size (AWG) | No. of Strands | Nom. OD (mils) (mm) | Nominal Total Weight (lbs/1000') (kgs/km) | Allowable Ampacity | |
890105 |
1
1
|
1/0 AWG
1/0 AWG
|
19
19
|
80
2.03
|
|
|
530
13.46
|
396
590
|
|
890106 |
1
1
|
2/0 AWG
2/0 AWG
|
19
19
|
80
2.03
|
|
|
572
14.53
|
488
727
|
|
890631 |
1
1
|
3/0 AWG
3/0 AWG
|
19
19
|
80
2.03
|
|
|
624
15.85
|
604
899
|
|
890107 |
1
1
|
4/0 AWG
4/0 AWG
|
19
19
|
80
2.03
|
|
|
680
17.27
|
748
1114
|
|
890632 |
1
1
|
250 KCMIL
250 KCMIL
|
37
37
|
95
2.41
|
|
|
742
18.85
|
892
1328
|
|
890108 |
1
1
|
350 KCMIL
350 KCMIL
|
37
37
|
95
2.41
|
|
|
861
21.87
|
1224
1821
|
|
890109 |
1
1
|
500 KCMIL
500 KCMIL
|
37
37
|
95
2.41
|
|
|
966
24.54
|
1707
2541
|
|
890633 |
1
1
|
750 KCMIL
750 KCMIL
|
61
61
|
110
2.79
|
|
|
1200
30.48
|
2551
3797
|
|