Armorlite® Type MC

PVC Jacketed


Lightweight Aluminum Interlocked Armor with Overall PVC Jacket. 600 Volts.

Copper Power Conductors. THHN/THWN Insulated Singles.

Sunlight Resistant. Green Insulated Grounding Conductor.

Sizes AWG 14 through AWG 2.  Rated VW-1.

Product Image

 

 

APPLICATIONS

 

Southwire Armorlite® Type MC Cable - "flame retardant sunlight resistant PVC Jacket" is suitable for use as follows: 

 

STANDARDS & REFERENCES

 Southwire's Armorlite Type MC Cable - Multi-Circuit comply with the following:  

 

CONSTRUCTION

 

Southwire Armorlite® Type MC Cable - "PVC Jacketed" is constructed with soft-drawn, copper Type THHN/THWN conductors rated 90°C dry/ 75°C wet, and a green insulated grounding conductor.  The conductors are cabled together and a binder tape is wrapped around the assembly.  Aluminum interlocking armor is applied over the assembly.  A black flame retardant PVC jacket is applied over the armor.  The jacket is available in other colors upon request subject to economic order quantites.  The standard PVC Jacket will not meet "Limited Smoke" or "LS" Rating. An optional SOLONON Jacket can be provided for "LS" Rating.

Conductor Size+ (AWG)

Solid or Stranded*

Grounding Conductor Size (AWG)

Outside Diameter Over Armor (inches)

Outside Diameter Over Jacket (inches)

Total Weight (Ibs/1000 ft.)

Ampacities‡ (Amps)

Standard Package

 

60°C

75°C

90°C

Coil (feet)

Reel (feet)

14/2

Solid

14 sol

0.439

0.539

122

15

15

15

250

1000

14/3

Solid

14 sol

0.464

0.565

142

15

15

15

250

1000

14/4

Solid

14 sol

0.494

0.594

162

15

15

15

250

1000

12/2

Solid

12 sol

0.475

0.575

152

20

20

20

250

1000

12/3

Solid

12 sol

0.505

0.605

180

20

20

20

250

1000

12/4

Solid

12 sol

0.539

0.639

209

20

20

20

250

1000

10/2

Solid

10 sol

0.542

0.642

204

30

30

30

250

1000

10/3

Solid

10 sol

0.580

0.680

247

30

30

30

250

1000

10/4

Solid

10 sol

0.623

0.723

291

30

30

30

250

1000

12/2

19

12-19

0.564

0.664

178

20

20

20

----

1000

12/3

19

12-19

0.602

0.702

217

20

20

20

----

1000

12/4

19

12-19

0.680

0.780

272

20

20

20

----

1000

10/2

19

10-19

0.653

0.753

245

30

30

30

----

1000

10/3

19

10-19

0.701

0.801

344

30

30

30

----

1000

10/4

19

10-19

0.799

0.899

436

30

30

30

250

1000

8/2

19

10-19

0.678

0.778

302

40

50

55

200

500

8/3

19

10-19

0.732

0.832

379

40

50

55

200

500

8/4

19

10-19

0.793

0.893

455

40

50

55

200

500

6/2

19

8-19

0.756

0.856

411

55

65

75

125

500

6/3

19

8-19

0.819

0.919

521

55

65

75

125

500

6/4

19

8-19

0.890

0.990

631

55

65

75

100

500

4/3

19

8-19

0.986

1.086

731

70

85

95

100

500

4/4

19

8-19

1.077

1.177

903

70

85

95

100

500

2/3

19

6-19

1.130

1.231

1042

95

115

130

100

500

2/4

19

6-19

1.239

1.339

1302

95

115

130

100

500

Note: Ampacities are based on Table 310.16 of the NEC, 2011 Edition.

‡Allowable ampacities shown are for general use as specified by the National Electrical Code, 2011 Edition, Section 310.15.

If the equipment is marked for use at higher temperatures, the conductor ampacity shall be limited to the following per NEC 110.14(C).
60°C - When terminated to equipment for circuits rated 100 amperes or less or marked for size 14 through 1 AWG conductors.
75°C - When terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than size 1 AWG.
90°C - For ampacity derating purposes.

Per NEC 310.15(B)(2)(a), the ampacity of 4/C cables shall be reduced by a factor of 0.80 when the neutral is considered a current-carrying conductor.

*Circuit sizes 12 AWG and 10 AWG also available as stranded conductors.
+ Available in sizes up to 750 kcmil.

 